O4: Maintenance Monitor Settings - YASKAWA U1000 Series Technical Manual

Low harmonics regenerative matrix converter
Hide thumbs Also See for U1000 Series:
Table of Contents

Advertisement

o3-02 Copy Allowed Selection
Restricts or allows the use of the Copy function.
No.
o3-02
Setting 0: Disabled
Setting 1: Enabled

◆ o4: Maintenance Monitor Settings

o4-01: Cumulative Operation Time Setting
Parameter o4-01 sets the cumulative operation time of the drive. The user can also manually set this parameter to begin
keeping track of operation time from some desired value. Total operation time can be viewed in monitor U4-01.
Note: The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h
will also be displayed in monitor U4-01.
No.
o4-01
o4-02: Cumulative Operation Time Selection
Selects the conditions for how the drive keeps track of its total operation time. This time log can be viewed in U4-01.
No.
o4-02
Setting 0: Power on time
The drive logs the time it is connected to a power supply, regardless if the motor is running or not.
Setting 1: Run time
The drive logs the time that the output is active. This includes whenever the Run command is active (even if the motor is
not rotating) and when there is voltage output.
o4-03: Cooling Fan Operation Time Setting
Sets the value for how long the cooling fan has been operating. This value can be viewed in monitor U4-03. Parameter
o4-03 also sets the base value used for the cooling fan maintenance, which is displayed in U4-04. Be sure to reset this
parameter back to 0 if the cooling fan is replaced.
Note: 1. The value in o4-03 increases after every 10 hours of use. A setting of 30 will set the cooling fan operation time counter to 300 h.
"300" will be displayed in monitor U4-03.
2. The cooling fan may require maintenance at an earlier date in harsher environments.
No.
o4-03
o4-05: Capacitor Maintenance Setting
Sets value of the maintenance monitor for the capacitors displayed in U4-05 as a percentage of the total expected
performance life. This value should be reset to 0 when the capacitors have been replaced.
Note: The actual maintenance time will depend on the environment where the drive is used.
No.
o4-05
YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
Name
Copy Allowed Selection
Name
Cumulative Operation Time Setting
Name
Cumulative Operation Time Selection
Name
Cooling Fan Operation Time Setting
Name
Capacitor Maintenance Setting
5.10 o: Operator Related Settings
Setting Range
0 or 1
Setting Range
0 to 9999
Setting Range
0 or 1
Setting Range
0 to 9999
Setting Range
0 to 150%
Default
0
Default
0
Default
0
Default
0
5
Default
0%
335

Advertisement

Table of Contents
loading

Table of Contents