Output Terminals

Table 3.11
lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function
output.
Type
Fault Relay Output
Multi-Function Digital Output
<1>
Multi-Function Photocoupler Output
<3>
Monitor Output
Safety Monitor Output
<1> Refrain from assigning functions to digital relay outputs that involve frequent switching, as doing so may shorten relay performance life.
Switching life is estimated at 200,000 times (assumes 1 A, resistive load).
<2> Terminals M3 to M6 are available only in CIMR-UB.
<3> Multi-Function Photocoupler Output is available only in CIMR-UA/UD/UT.
<4> Connect a suppression diode as shown in the
than the circuit voltage.
Figure 3.37
Serial Communication Terminals
Type
No.
R+
R-
MEMOBUS/Modbus
Communication
S+
<1>
S-
IG
<1> Enable the termination resistor in the last drive in a MEMOBUS/Modbus network by setting DIP switch S2 to the ON position. For more
information on the termination resistor, see
YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
Table 3.11 Control Circuit Output Terminals
No.
Terminal Name (Function)
N.O. output (Fault)
MA
N.C. output (Fault)
MB
Fault output common
MC
M1
Multi-function digital output (During run)
M2
M3
<2>
Multi-function digital output (Zero Speed)
M4
<2>
M5
<2>
Multi-function digital output (Speed Agree 1)
M6
<2>
Photocoupler output 1 (Zero speed)
P1
Photocoupler output 2 (Speed agree 1)
P2
Photocoupler output common
PC
Pulse train output (Output frequency)
MP
Analog monitor output 1 (Output frequency)
FM
AM
Analog monitor output 2 (Output current)
AC
Monitor common
DM+
Safety monitor output
Safety monitor output
DM-
Figure 3.36
when driving a reactive load such as a relay coil. Make sure the diode rating is greater
A
A – External power, 48 V max.
B – Suppression diode
Figure 3.36 Connecting a Suppression Diode
Table 3.12 Control Circuit Terminals: Serial Communications
Signal Name
Communications input (+)
Communications input (-)
MEMOBUS/Modbus communication: Use a RS-485 or
RS-422 cable to connect the drive.
Communications output (+)
Communications output (-)
Shield ground
Control I/O Connections on page
Function (Signal Level) Default Setting
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
48 Vdc, 2 to 50 mA
32 kHz (max)
-10 to +10 Vdc, 0 to +10 Vdc
Resolution: 1/1000
0 V
Outputs status of Safe Disable function. Closed when
both Safe Disable channels are closed. Up to +48 Vdc
50 mA.
B
C
D
C – Coil
D – 50 mA or less
Function (Signal Level)
110.
3.9 Control Circuit Wiring
<3>
RS-422/RS-485
MEMOBUS/Modbus communication protocol
115.2 kbps (max.)
0 V
Page
276