5.6 F: Option Settings
F6-01: Communications Error Operation Selection
Determines drive operation if a communication error occurs.
No.
F6-01
Setting 0: Ramp to stop (uses the deceleration time set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only (continue operation)
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option (EF0).
No.
F6-02
Setting 0: Always detected
Setting 1: Detection during run only
F6-03: External Fault from Comm. Option Operation Selection
Determines the operation when an external fault is initiated by a communication option (EF0).
No.
F6-03
Setting 0: Ramp to stop
Setting 1: Coast to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)
F6-06: Torque Reference/Torque Limit Selection from Comm. Option
Used to select if torque reference and torque limit values are assigned to the drive from the network.
No.
F6-06
Setting 0: Disabled
Setting 1: Enabled
F6-07: Multi-Step Speed Enable/Disable when NetRef/ComRef is Selected
Selects how multi-step speed inputs are treated when the NetRef command is set.
No.
F6-07
Setting 0: Multi-step speed operation disabled
If the NetRef command is selected, multi-step speed input frequency references are disabled.
Setting 1: Multi-step speed operation enabled
Even if the NetRef command is selected, multi-step speed inputs are still active and can override the frequency reference
from the communications option.
264
Parameter Name
Communications Error Operation Selection
Parameter Name
External Fault from Comm. Option Detection Selection
Parameter Name
External Fault from Comm. Option Operation Selection
Parameter Name
Torque Reference/Torque Limit Selection from Comm. Option
Parameter Name
Multi-Step Speed Enable/Disable when NetRef/ComRef is Selected
Setting Range
Setting Range
Setting Range
Setting Range
Setting Range
YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
Default
0 to 3
1
Default
0 or 1
Default
0 to 3
Default
0, 1
Default
0, 1
0
1
0
0