<7> Enable the termination resistor in the last drive in a MEMOBUS network by setting DIP switch S2 to the ON position.
<8> Use jumper S5 to selection between voltage or current output signals at terminal AM and FM. Set parameters H4-07 and H4-08 accordingly.
<9> Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters. They are not intended for use as a
feedback-type of signal.
<10> Use jumper S3 to select between Sink mode, Source mode or external power supply for the Safe Disable inputs.
<11> Disconnect the wire jumper between H1 - HC and H2 - HC when utilizing the Safe Disable input.
<12> Slide the switch S6 to select N.C. or N.O. as the state of the DM+ and DM- terminals for EDM output.
<13> Models CIMR-UP and W have terminals 24, 0, and FE. The main circuit power supply can be turned off separately
even when power is supplied to the control circuit.
NOTICE: Do not connect more than one multi-function input to one terminal. Improper wiring may result in drive malfunction. Use an
external power supply when sharing a terminal with more than one input. Do not use the built-in +24 V power supply.
NOTICE: Separate control circuit wiring from main circuit wiring and other high-power lines. Improper wiring practices could result in
drive malfunction due to electrical interference.
The main circuit terminals vary by the drive models.
CIMR-U20028 to 20248, 40011 to 40414: R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, p1, n1
CIMR-U40477 to 40930: X, Y, Z, X1, Y1, Z1, r1/ 11, 1/ 21, t1/ 31, U/T1, V/T2, W/T3, p1, n1, p2, n2
YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual