C.9 Memobus/Modbus Data Table - YASKAWA U1000 Series Technical Manual

Low harmonics regenerative matrix converter
Hide thumbs Also See for U1000 Series:
Table of Contents

Advertisement

C.9 MEMOBUS/Modbus Data Table

Table below lists all MEMOBUS/Modbus data. There are three types of data: command data, monitor data, and
broadcast data.
◆ Command Data
It is possible to both read and write command data.
Note: Bits that are not used should be set to 0. Refrain from writing to reserved registers.
Register No.
0000H
Reserved
Operation Commands and Multi-function Inputs
bit 0
bit 1
bit 2
bit 3
bit 4
0001H
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C to F
0002H
Frequency Reference
0003H
Output voltage gain
0004H
Torque Reference/Torque Limit, 0.1% units, signed (Usable only if Torque Control is enabled)
0005H
Torque Compensation, 0.1% units, signed (Usable only if Torque Control is enabled)
0006H
PID Target, 0.01% units, signed
0007H
Analog Output Terminal FM Setting (10 V / 4000 H)
0008H
Analog Output Terminal AM Setting (10 V / 4000 H)
Settings for Multi-Function Digital Outputs
bit 0
bit 1
bit 2
0009H
bit 3 to 5
bit 6
bit 7
bit 8 to F
000AH
Pulse Output Terminal MP Setting, 1 Hz units, Setting Range: 0 to 32000
000BH to 000EH
Reserved
Control Selection Setting
bit 0
bit 1
bit 2
bit 3
000FH
bit 4 to B
bit C
bit D
bit E
bit F
0010H to 001AH
Reserved
001BH
Analog Monitor Option AO-A3 Analog Output 1 (10 V/4000 H)
001CH
Analog Monitor Option AO-A3 Analog Output 2 (10 V/4000 H)
001DH
Digital Output Option DO-A3 Output (Binary)
001EH to 001FH
Reserved
YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
H5-12 = 0: Forward Run Command (0 = Stop, 1 = Forward Run)
H5-12 = 1: Run Command (0 = Stop, 1 = Run)
H5-12 = 0: Reverse Run Command (0 = Stop, 1 = Reverse Run)
H5-12 = 1: Forward/Reverse (0 = Forward, 1 = Reverse)
Option Card External Fault (EF0)
Fault Reset
Multi-Function Input 1
Function is ComRef when H1-01 = 40 (Forward/Stop).
Note: When the bit at ComCtrl is turned on, commands from MEMOBUS/Modbus communications take control of the operation.
However, when a communications option card is connected, that option card is given priority.
Multi-Function Input 2
Function is ComCtrl when H1-02 = 41 (Reverse/Stop).
Multi-Function Input 3
Multi-Function Input 4
Multi-Function Input 5
Multi-Function Input 6
Multi-Function Input 7
Multi-Function Input 8
Reserved
Units are determined by parameter o1-03.
Unit: 0.1%
Range: 20 (2.0%) to 2000 (200.0%), Default when power on: 1000 (100.0%)
Multi-Function Contact Output (terminal M1-M2)
CIMR-UA, CIMR-UD, CIMR-UT:Multi-Function Photocoupler Output 1 (terminal P1 - PC)
CIMR-UB:Multi-Function Contact Output 2 (terminal M3-M4)
CIMR-UA, CIMR-UD, CIMR-UT:Multi-Function Photocoupler Output 2 (terminal P2 - PC)
CIMR-UB:Multi-Function Contact Output 2 (terminal M5-M6)
Reserved
Enables the function in bit 7
Fault Contact Output (terminal MA/MB-MC)
Reserved
Reserved
PID Setpoint Input
Torque reference / torque limit input (enables the setting from MEMOBUS/Modbus)
Torque compensation input (enables the setting from MEMOBUS/Modbus)
Reserved
Enable Terminal S5 Input for Broadcast Data
Enable Terminal S6 Input for Broadcast Data
Enable Terminal S7 Input for Broadcast Data
Enable Terminal S8 Input for Broadcast Data
C.9 MEMOBUS/Modbus Data Table
Contents
C
571

Advertisement

Table of Contents
loading

Table of Contents