B.3 Parameter Table
No. (Addr.)
Name
U4-18
Frequency Reference Source
(7DAH)
Selection
U4-19
Frequency Reference from
(7DBH)
MEMOBUS/Modbus Comm.
U4-20
Option Frequency Reference
(7DCH)
U4-21
Run Command Source
(7DDH)
Selection
U4-22
MEMOBUS/Modbus
(7DEH)
Communications Reference
U4-23
Communication Option Card
(7DFH)
Reference
<19> Display is in the following units.
 CIMR-U20028, 20042, and 40011 to 40027: 0.01 A units
 CIMR-U20054 to 20248, and 40034 to 40720: 0.1 A units
 CIMR-U40900, 40930: 1 A units
<23> When checking the values of U1-03, U2-05 and U4-13 with the digital operator they are displayed in units of amperes, but when they are
checked using MEMOBUS/Modbus communications, the monitor value in MEMOBUS/Modbus communications is: displayed numeric value
/ 8192 × drive' rated current (A), from the condition "8192 (maximum value) = drive' rated current (A)"
<26> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 0099H.
<58> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 009BH.
528
All Modes
Displays the source for the frequency reference as XY-nn.
X: indicates which reference is used:
1 = Reference 1 (b1-01)
2 = Reference 2 (b1-15)
Y-nn: indicates the reference source
0-01 = Digital operator
1-00 = Analog
1-01 = Analog (terminal A1)
1-02 = Analog (terminal A2)
1-03 = Analog (terminal A3)
2-02 to 17 = Multi-step speed (d1-02 to 17)
3-01 = MEMOBUS/Modbus communications
4-01 = Communication option card
5-01 = Pulse input
7-01 = DWEZ
9-01 = Up/Down Command
All Modes
Displays the frequency reference provided by MEMOBUS/Modbus (decimal).
All Modes
Displays the frequency reference input by an option card (decimal).
All Modes
Displays the source for the Run command as XY-nn.
X: Indicates which Run source is used:
1 = Reference 1 (b1-02)
2 = Reference 2 (b1-16)
Y: Input power supply data
0 = Digital operator
1 = External terminals
3 = MEMOBUS/Modbus communications
4 = Communication option card
7 = DWEZ
nn: Run command limit status data
00: No limit status.
01: Run command was left on when stopped in the PRG mode
02: Run command was left on when switching from LOCAL to REMOTE operation
03: Waiting for soft charge bypass contactor after power up (Uv or Uv1 flashes after 10 s)
04: Waiting for "Run command prohibited" time period to end
05: Fast Stop (digital input, digital operator)
06: b1-17 (Run command given at power-up)
07: During baseblock while coast to stop with timer
08: Frequency reference is below minimal reference during baseblock
09: Waiting for Enter command
All Modes
Displays the drive control data set by MEMOBUS/Modbus communications register no. 0001H
as a four-digit hexadecimal number.
All Modes
Displays drive control data set by an option card as a four-digit hexadecimal number.
Description
YASKAWA ELECTRIC SIEP C710636 02B YASKAWA U1000 Technical Manual
Analog Output
Unit
Page
Level
No signal output
available
No signal output
0.01%
available
No signal output
available
No signal output
available
No signal output
available
No signal output
available