3.7 Top Protective Cover

3.7
Top Protective Cover
Drive models with IP00 specifications become IP20/NEMA 1, UL Type 1 after correctly installing a top protective cover.
Do not attach the top protective cover when installing the drive in a control panel.
◆ Attaching the Top Protective Cover
Insert the small protruding hooks on the sides of the top protective cover into the provided mounting holes on the top of
the drive. Pinch the hooks inward so that the they connect with the mounting holes and fasten the top protective cover
back into place.
Note: Attaching the top protective cover and the bottom conduit bracket to an IP00 drive changes protection to IP20/NEMA 1, UL
Type 1.
Figure 3.28
◆ Removing the Top Protective Cover
Insert the tip of a straight-edge screwdriver into the small opening located on the front edge of the top protective cover.
Gently apply pressure as shown in the figure below to free the cover from the drive.
Note: Removing the top protective cover or the bottom conduit bracket from an IP20/NEMA 1, UL Type 1 enclosure drive voids the
NEMA 1, UL Type 1 protection while maintaining IP20 conformity.
Figure 3.29
88
A – Protective Cover Mounting Holes
Figure 3.27 Reattaching the Top Protective Cover