3.4 Components for the Power Modules
3.4.4

Output reactor

Output reactors reduce the voltage stress on
the motor windings and the load placed on the
inverter as a result of capacitive recharging
currents in the cables. An output reactor is
required for shielded motor cables longer than
50 m or unshielded motor cables longer than
100 m.
NOTICE
The output reactor is damaged if the inverter pulse frequency is too high
The output reactors are designed for pulse frequencies of 4 kHz. The output reactor can
overheat if the inverter is operated with pulse frequencies > 4 KHz. Excessively high
temperatures damage the output reactor.
• Operate the inverter with an output reactor with a maximum pulse frequency of 4 kHz.
Output reactors for PM240 Power Module
Power Module
FSA
FSB
FSC
FSD
FSE
FSF
40
6SL3224-0BE13-7UA0,
6SL3224-0BE15-5UA0,
6SL3224-0BE17-5UA0,
6SL3224-0BE21-1UA0,
6SL3224-0BE21-5UA0
6SL3224-0BE22-2☐A0,
6SL3224-0BE23-0☐A0,
6SL3224-0BE24-0☐A0
6SL3224-0BE25-5☐A0,
6SL3224-0BE27-5☐A0,
6SL3224-0BE31-1☐A0
6SL3224-0BE31-5☐A0
6SL3224-0BE31-8☐A0
6SL3224-0BE32-2☐A0
6SL3224-0BE33-0☐A0
6SL3224-0BE33-7☐A0
6SL3224-0BE34-5☐A0
6SL3224-0BE35-5☐A0
6SL3224-0BE37-5☐A0
6SL3224-0BE38-8UA0
6SL3224-0BE41-1UA0
for PM240 FSA, FSB
Power
0.37 kW ... 1.5 kW
2.2 kW ... 4.0 kW
7.5 kW ... 15.0 kW
18.5 kW
22 kW
30 kW
37 kW
45 kW
55 kW
75 kW
90 kW
110 kW
132 kW
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
for GX
Output reactor
6SE6400-3TC00-4AD2
6SL3202-0AE21-0CA0
6SL3202-0AJ23-2CA0
6SE6400-3TC05-4DD0
6SE6400-3TC03-8DD0
6SE6400-3TC05-4DD0
6SE6400-3TC08-0ED0
6SE6400-3TC07-5ED0
6SE6400-3TC14-5FD0
6SE6400-3TC15-4FD0
6SE6400-3TC14-5FD0
6SL3000-2BE32-1AA0
6SL3000-2BE32-6AA0