Siemens SINAMICS G120 Operating Instructions Manual page 415

Low voltage converter with the cu240b-2 and cu240e-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Table 9- 8
The most important alarms and faults
Number
Cause
F01018
Power-up aborted more than once
A01028
Configuration error
F01033
Switching over units: Reference
parameter value invalid
F01034
Switching over units: Calculation of
the parameter values after refer-
ence value change unsuccessful
A01053
System overload measured
F01054
System limit exceeded
F01122
Frequency at the probe input too
high
A01590
Motor maintenance interval
elapsed
A01900
PROFIBUS: Configuration tele-
gram faulty
A01910
Setpoint timeout
F01910
A01920
PROFIBUS: Cyclic connection
interrupt
F03505
Analog input, wire-break
A03520
Temperature sensor fault
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Remedy
1. Switch the module off and on again.
2. After this fault has been output, the module is booted with the factory
settings.
3. Recommission the inverter.
Explanation: Parameterization on the memory card has been created with
a different type of module (Article number, MLFB).
Check the module parameters and recommission if necessary.
Set the value of the reference parameter not equal to 0.0 (p0304, p0305,
p0310, p0596, p2000, p2001, p2002, p2003, r2004).
Select the value of the reference parameter so that the parameters in-
volved can be calculated in the per unit notation (p0304, p0305, p0310,
p0596, p2000, p2001, p2002, p2003, r2004).
The maximum computing power of the Control Unit was exceeded. The
following measures reduce the load on the Control Unit:
Use only one data record (CDS and DDS)
Only use the safety features of the basic functions
Deactivate the technology controller
Use the simple ramp-function generator rather than the extended
ramp-function generator
Do not use any free function components
Reduce the sampling time of the free function blocks
Reduce the frequency of the pulses at the probe input.
Carry out maintenance and reset the maintenance interval (p0651).
Explanation: A PROFIBUS master is attempting to establish a connection
with a faulty configuration telegram.
Check the bus configuration on the master and slave side.
The alarm is generated when p2040 ≠ 0 ms and one of the following
causes is present:
The bus connection is interrupted
The Modbus master is switched off
Communications error (CRC, parity bit, logical error)
An excessively low value for the fieldbus monitoring time (p2040)
Explanation: The cyclic connection to PROFIBUS master is interrupted.
Establish the PROFIBUS connection and activate the PROFIBUS master
with cyclic operation.
Check the wiring for interruptions.
Check the level of the injected signal.
The input current measured by the analog input can be read out in r0752.
Check that the sensor is connected correctly.
Alarms, faults and system messages
9.5 List of alarms and faults
415

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents