Dimensioned drawings, drilling dimensions for the PM240 Power Module,
FSGX
Mount the Power Module with the following clearances to other devices:
● Top: 250 mm
● Bottom: 150 mm
● Lateral: no clearance required for thermal reasons.
Fasten the Power Module with six M8 screws with a tightening torque of 13 Nm.
68
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC