Siemens SINAMICS G120 Operating Instructions Manual page 199

Low voltage converter with the cu240b-2 and cu240e-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Status word 3 (ZSW3)
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Significance
1 = DC braking active
1 = |n_act | > p1226
1 = |n_act | > p1080
1 = i_act ≧ p2170
1 = |n_act | > p2155
1 = |n_act | ≦ p2155
1 = |n_act | ≧ r1119
1 = DC link voltage ≦ p2172
1 = DC link voltage > p2172
1 = ramp-up or ramp-down complet-
ed
1 = technology controller output at
the lower limit
1 = technology controller output at
the upper limit
Not used
Not used
Not used
Not used
Description
--
Absolute current speed > stationary
state detection
Absolute actual speed > minimum
speed
Actual current ≥ current threshold
value
Absolute actual speed > speed
threshold value 2
Absolute actual speed < speed
threshold value 2
Speed setpoint reached
Actual DC link voltage ≦ threshold
value
Actual DC link voltage > threshold
value
Ramp-function generator is not
active.
Technology controller output ≦
p2292
Technology controller out-
put > p2291
Advanced commissioning
6.2 Inverter control
Signal intercon-
nection in the
inverter
p2051[3] = r0053
199