Technical data
10.3 Technical data, Power Modules
Table 10- 9
PM240-2, IP20, FSE, 3 AC 200 V ... 240 V
Article No. - without filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
Power loss
Required cooling air flow
Weight
Table 10- 10 PM240-2, IP20, FSF, 3 AC 200 V ... 240 V
Article No. - without filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
Power loss
Required cooling air flow
Weight
436
6SL3210-...
...1PC28-8UL0
22 kW
76 A
80 A
18.5 kW
71 A
68 A
3 NE1 021-0 / 100A
100 A
0.85 kW
83 l/s
26 kg
6SL3210-...
...1PC31-3UL0
37 kW
126 A
130 A
30 kW
110 A
104 A
3 NE1 225-0 / 200A
175 A
1.44 kW
153 l/s
57 kg
...1PC31-1UL0
30 kW
98 A
104 A
22 kW
83 A
80 A
3 NE1 224-0 / 160A
150 A
1.20 kW
83 l/s
26 kg
...1PC31-6UL0
45 kW
149 A
154 A
37 kW
138 A
130 A
3 NE1 225 -0 / 200A
200 A
1.79 kW
153 l/s
57 kg
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
...1PC31-8UL0
55 kW
172 A
178 A
45 kW
164 A
154 A
3 NE1 227-0 / 250A
225 A
2.18 kW
153 l/s
57 kg