Dimensioned drawings, drilling dimensions for the PM340 Power Module

The following dimensioned drawings and drilling patterns are not to scale.
Image 4-1
The Power Modules can be mounted and operated side-by-side. For tolerance reasons, we
recommend a lateral clearance of approx. 1 mm.
Cooling clearances and fastening
● Top cooling clearance: 100 mm
● Bottom cooling clearance:
● Front cooling clearance:
● For fastening:
Depth with Control Unit and Operator Panel
• with Control Unit:
• With Control Unit and blanking cover / BOP-2:
• With Control Unit and IOP:
76
Mounting dimensions and drilling dimensions (mm)
100 mm
65 mm
2 x M4 / 2.5 Nm
186 mm
197 mm
208 mm
Converter with the CU240B-2 and CU240E-2 Control Units