Siemens SINAMICS G120 Operating Instructions Manual page 313

Low voltage converter with the cu240b-2 and cu240e-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Parameter
p2350
p2354
p2355
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Remark
PID Autotune Enable (Factory setting: 0)
Automatic controller setting based on the "Ziegler Nichols" method.
After completion of the autotuning, the inverter sets p2350 = 0.
0:
No function
1:
Controller setting after completion of the autotuning:
The process variable follows the setpoint after a sud-
den setpoint change (step function) relatively quickly,
however with an overshoot.
2:
Faster controller setting than for p2350 = 1 with larger
overshoot of the controlled variable.
3:
Slower controller setting than for p2350 = 1. Overshoot
of the controlled variable is, to a large extent, avoided.
4:
Controller setting after completion of the autotuning as
for p2350 = 1. Optimize only the P and I action of the
PID controller.
PID tuning timeout length (Factory setting: 240 s)
Monitoring time for the process response.
p2354 must be greater than half the time period of the process variable oscillation.
PID tuning offset (Factory setting: 5%)
Autotuning offset.
p2355 must be sufficiently large so that the amplitude of the process variable oscil-
lation signal can be differentiated from any superimposed noise.
Advanced commissioning
6.7 Application-specific functions
313