9. Set the check mark for "RAM to ROM (save data in the drive)" to save your data in the
You have completed quick commissioning.
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Motor identification:
• [1]: Recommended setting. Measure the motor data at standstill and
with the motor rotating. The inverter switches off the motor after the
motor data identification has been completed.
• [2]: Measure the motor data at standstill. The inverter switches off
the motor after the motor data identification has been completed.
Recommended setting for the following cases:
– You have selected "Speed control" as control mode, however the
– You have set "V/f control" as control mode.
• [3]: Measure the motor data while it is rotating. The inverter switches
off the motor after the motor data identification has been completed.
• [11]: The same setting as [1]. The motor accelerates to the currently
set setpoint after the motor data identification.
• [12]: The same setting as [2]. The motor accelerates to the currently
set setpoint after the motor data identification.
Calculating the motor parameters: Select "Complete calculation".
inverter so that it is not lost when the power fails.
Select "Finish".
Exiting quick commissioning in STARTER
Exiting quick commissioning in Startdrive
motor cannot freely rotate, e.g. for mechanically limited traversing
sections.
Commissioning
5.4 Quick commissioning with a PC.
157