Technical data
10.3 Technical data, Power Modules
Table 10- 5
PM240-2, IP 20, frame sizes C, 1 AC / 3 AC 200 V ... 240 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current 1 AC
LO base load input current 3 AC
LO base load output current
HO base load power
HO base load input current 1 AC
HO base load input current 3 AC
HO base load output current
Fuse according to IEC
Fuse according to UL
Power losses without filter
Power losses with filter
Required cooling air flow
Weight without filter
Weight with filter
Table 10- 6
PM240-2, PT, frame sizes C, 1 AC / 3 AC 200 V ... 240 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current 1 AC
LO base load input current 3 AC
LO base load output current
HO base load power
HO base load input current 1 AC
HO base load input current 3 AC
HO base load output current
Fuse according to IEC
Fuse according to UL
Power losses without filter
Power losses with filter
Required cooling air flow
Weight without filter
Weight with filter
1) approx. 0.09 through the heatsink
434
6SL3210...
...1PB21-4UL0
6SL3210...
...1PB21-4AL0
3 kW
35.9 A
17.7 A
13.6 A
2.2 kW
31.3 A
13.6 A
10.4 A
3NE 1817-0 (50 A)
50 A Class J
0.14 kW
0.14 kW
18.5 l/s
5.0 kg
5.2 kg
6SL3211...
...1PB21-8UL0
...1PB21-8AL0
6SL3211...
4 kW
43.0 A
22.8 A
17.5 A
3 kW
37.5 A
17.7 A
13.6 A
3NE 1818-0 (63 A)
50 A Class J
0.18 kW
0.18 kW
18.5 l/s
5.9 kg
6.2 kg
...1PB21-8UL0
...1PB21-8AL0
4 kW
43.0 A
22.8 A
17.5 A
3 kW
37.5 A
17.7 A
13.6 A
3NE 1818-0 (63 A)
50 A Class J
0.18 kW
0.18 kW
18.5 l/s
5.0 kg
5.2 kg
1)
1)