General Data, Pm240 - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converter with the cu240b-2 and cu240e-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Technical data
10.3 Technical data, Power Modules
10.3.2.1

General data, PM240

Property
Line voltage
Output voltage
Input frequency
Output frequency
Power factor λ
Inrush current
Overvoltage category ac-
cording to EN 60664-1
Short-circuit current rating
(SCCR)
Pulse frequency (factory
setting)
Electromagnetic compatibil-
ity
Braking methods
Degree of protection ac-
cording to EN 60529
Environmental conditions for transport in the transport packaging
Climatic environmental
conditions
Mechanical environmental
conditions (shocks and
vibrations)
Protection against chemical
substances
Biological environmental
conditions
Environmental conditions for long-term storage in the product packaging
Climatic environmental
conditions
Mechanical environmental
conditions (shocks and
vibrations)
Protection against chemical
substances
Biological environmental
conditions
452
Version
3-phase 380 ... 480 VAC ± 10%
3-phase 0 VAC ... input voltage x 0.95 (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 Hz ... 550 Hz, depending on the control mode
0.7 ... 0.85
< LO base load input current
The inverter insulation is designed for surge voltages according to overvoltage Category III.
≤ 65 kA rms
4 kHz for devices with an LO base load power ≤ 90 kW
2 kHz for devices with an LO base load power > 90 kW
Can be set in 2 kHz steps in the range 2 kHz ... 16 kHz.
If you increase the pulse frequency, the inverter reduces the maximum output current.
Current derating depending on the pulse frequency (Page 459)
The devices are suitable for environments of categories C1 and C2 according to IEC/EN
61800-3.
DC braking, compound braking, dynamic braking with integrated braking chopper
IP20
Installation in a control cabinet required
The device is suitable for temperatures that conform with 2K4 according to EN 60721-3-2 in
the range -40° ... +70° C
The device is suitable for operation in mechanical environmental conditions that conform
with 2M3 according to EN 60721-3-2
The device is protected against damaging chemical substances that conform with 2C2 ac-
cording to EN 60721-3-2
The device is suitable for operation in biological environmental conditions that conform with
2B2 according to EN 60721-3-2
The device is suitable for temperatures that conform with 1K4 according to EN 60721-3-1 in
the range -25° ... +55° C
The device is suitable for operation in mechanical environmental conditions that conform
with 1M2 according to EN 60721-3-1
The device is protected against damaging chemical substances that conform with 1C2 ac-
cording to EN 60721-3-1
The device is suitable for operation in biological environmental conditions that conform with
1B2 according to EN 60721-3-1
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC