Advertisement

6.2.2.3

Digital outputs

Changing the function of a digital output
Not available with Control Units CU240B-2 and CU240B-2 DP
1)
Table 6- 2
0
r0052.0
r0052.1
r0052.2
r0052.3
r0052.4
r0052.5
r0052.6
r0052.7
r0052.8
The complete list of binector outputs is provided in the List Manual.
Changing the function of a digital output - Example
Advanced settings
You can invert the signal of the digital output using parameter p0748.
For more information, please see the parameter list and the function block diagrams 2230 f
of the List Manual.
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Binector outputs (BO) of the inverter (selection)
Deactivating digital output
Drive ready
Drive ready for operation
Drive running
Drive fault active
OFF2 active
OFF3 active
Closing lockout active
Drive alarm active
Setpoint/actual value discrepancy
To output inverter fault messages via digital output DO 1,
you must interconnect DO1 with the fault messages: Set
p0731 = 52.3.
To change the function of a digital output, you
must interconnect the digital output with a binector
output of your choice.
Interconnecting signals in the inverter
(Page 495)
Binector outputs are marked with "BO" in the pa-
rameter list of the List Manual.
r0052.9
Process data control
r0052.10
f_actual >= p1082 (f_max)
r0052.11
Alarm: Motor current/torque limit
r0052.12
Brake active
r0052.13
Motor overload
r0052.14
Motor CW rotation
r0052.15
Inverter overload
r0053.0
DC braking active
r0053.2
f_actual > p1080 (f_min)
r0053.6
f_actual ≥ setpoint (f_setpoint)
Advanced commissioning
6.2 Inverter control
177