7. Proceed as follows:
You have transferred an inverter accessible via the USB interface into your project.
Setting the USB interface in STARTER
Procedure
Proceed as follows to set the USB interface in STARTER:
1. Set the "Access point" to "DEVICE (STARTER, Scout)" and the "PG/PC interface" to
"S7USB".
2. Press the "Update" button.
You have set the USB interface.
STARTER now shows the inverters connected via USB.
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
With STARTER
Select the inverter ☑.
Press the "Accept" button.
5.4 Quick commissioning with a PC.
With Startdrive
Transfer the inverter into the project using the menu:
"Online - Upload device as new station (hardware and
software)".
Commissioning
149