Advanced commissioning
6.2 Inverter control
For more information, please see the parameter list and the function block diagrams 2261 of
the List Manual.
Defining the function of an analog output - example
Advanced settings
You can manipulate the signal that you output via an analog output, as follows:
● Absolute-value generation of the signal (p0775)
● Signal inversion (p0782)
Additional information is provided in the parameter list of the List Manual.
184
To output the inverter output current via analog output 0, you
must interconnect AO 0 with the signal for the output current:
Set p0771 = 27.
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC