Depth with Control Unit and Operator Panel
• with Control Unit:
• With Control Unit and blanking cover / BOP-2:
• With Control Unit and IOP:
Table 4- 6
Frame size
FSA
FSB without/with filter
FSC without/with filter
FSD without filter
FSD with filter
FSE without filter
FSE with filter
FSF without filter
FSF with filter
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Drilling dimensions, cooling clearances and fixing
Drilling dimensions (mm)
b
h
36.5
160
133
258
167
323
235
325
235
419
235
405
235
541
300
598
300
898
4.4 Installing Power Modules
+ 41 mm
+ 52 mm
+ 63 mm
Cooling air clearances (mm)
c
Top
Bottom
7.5
100
100
5.5
100
100
6
125
125
11
300
300
11
300
300
11
300
300
11
300
300
11
350
350
11
350
350
Installing
Mounting
Front
Screws/torque
(Nm)
65
2 x M4 / 2.5
65
4 x M4 / 2.5
65
4 x M5 / 3.0
65
4 x M6 / 6.0
65
4 x M6 / 6.0
65
4 x M6 / 10
65
4 x M6 / 10
65
4 x M8 / 13
65
4 x M8 / 13
67