Table 10- 39 PM230, IP20, frame sizes A, 3 AC 380 V ... 480 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL
Power loss
Required cooling air flow
Cross section of line and motor cables
Tightening torque for line and motor cables
Weight without filter
Weight with filter
Table 10- 40 PM230, PT, frame sizes A, 3 AC 380 V ... 480 V
Article No. - without filter
Article No. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL
Power loss
Required cooling air flow
Cross section of line and motor cables
Tightening torque for line and motor cables
Weight without filter
Weight with filter
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
6SL3210...
...1NE17-7UL1
6SL3210...
...1NE17-7AL1
3 kW
8.0 A
7.7 A
2.2 kW
6.1 A
5.9 A
3NE1 813-0
AJT10 / 3NE1 813-0
0.11 kW
4.5 l/s
1.5 ... 2.5 mm
16 ... 14 AWG
0.5 Nm / 4 lbf in
1.4 kg
1.6 kg
6SL3211...
...1NE17-7UL1
6SL3211...
...1NE17-7AL1
3 kW
8.0 A
7.7 A
2.2 kW
6.1 A
5.9 A
3NE1 813-0
AJT10 / 3NE1 813-0
0.11 kW
4.5 l/s
1.5 ... 2.5 mm
16 ... 14 AWG
0.5 Nm / 4 lbf in
1.7 kg
1.9 kg
10.3 Technical data, Power Modules
2
2
Technical data
463