Article number
6SL3210-1PB13-0❒L0
6SL321❒-1PB13-8❒L0
6SL3211-1PB15-5❒L0
6SL3210-1PB17-4❒L0
6SL321❒-1PB21-0❒L0
6SL3210-1PB21-4❒L0
6SL321❒-1PB21-8❒L0
6SL3210-1PC22-2❒L0
6SL3210-1PC22-8❒L0
6SL3210-1PC24-2❒L0
6SL3210-1PC25-4❒L0
6SL3210-1PC26-8❒L0
6SL3210-1PC28-8❒L0
6SL3210-1PC31-1❒L0
6SL3210-1PC31-3❒L0
6SL3210-1PC31-6❒L0
6SL3210-1PC31-8❒L0
The permissible motor cable length depends on the particular cable type and the pulse frequency that
has been selected
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
LO base load output current for a pulse frequency of ...
2 kHz /
6 kHz
8 kHz
4 kHz
3.2
2.6
2.1
4.2
3.3
2.7
6.0
4.7
3.9
7.4
6.3
5.2
10.4
8.8
7.3
13.6
11.6
9.5
17.5
14.9
12.3
22.0
18.7
15.4
28.0
23.8
19.6
42
35.7
29.4
54
45.9
37.8
68
57.8
47.6
80
68.0
56.0
104
88.4
72.8
130
110.5
91.0
154
130.9
107.8
178
151.3
124.6
Technical data
10.3 Technical data, Power Modules
[A]
10 kHz
12 kHz
14 kHz
1.8
1.5
1.4
2.3
2.0
1.8
3.3
2.8
2.5
4.4
3.7
3.3
6.2
5.2
4.7
8.2
6.8
6.1
10.5
8.8
7.9
13.2
11.0
9.9
16.8
14.0
12.6
25.2
21.0
18.9
32.4
27.0
24.3
40.8
34.0
30.6
48.0
40.0
36.0
62.4
52.0
46.8
---
---
---
---
---
---
---
---
---
16 kHz
1.2
1.6
2.2
3.0
4.2
5.4
7.0
8.8
11.2
16.8
21.6
27.2
32.0
41.6
---
---
---