Siemens SINAMICS G120 Operating Instructions Manual page 140

Low voltage converter with the cu240b-2 and cu240e-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Commissioning
5.3 Quick commissioning using the BOP-2 operator panel
11.
12.
13.
14.
15.
16.
17.
You have completed quick commissioning.
140
Minimum and maximum motor speed
Motor ramp-up time
Motor ramp-down time
Ramp-down time for the OFF3 command
Motor data identification
Select the method which the inverter uses to measure the data of the
connected motor:
OFF
STIL ROT Recommended setting: Measure the motor data at stand-
STILL
ROT
ST RT OP Setting the same as STIL ROT.
STILL OP
Complete quick commissioning:
17.1. Switch over the display using an arrow key: nO → YES
17.2. Press the OK key.
Motor data is not measured.
still and with the motor rotating.
The inverter switches off the motor after the motor data
identification has been completed.
Measure the motor data at standstill.
The inverter switches off the motor after the motor data
identification has been completed.
Select this setting if the motor cannot rotate freely – for
example, if the traversing range is mechanically limited.
Measure the motor data while it is rotating.
The inverter switches off the motor after the motor data
identification has been completed.
The motor accelerates to the currently set setpoint after
the motor data identification.
Setting the same as STILL.
After the motor data identification, the motor accelerates
to the currently set setpoint.
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC