NOTE:
Charge the instrument fully before use (see § 5.1)

3.1 SERIAL NUMBER

To view the serial number of the instrument, keep the DISPLAY button pressed
and turn the switch to the MΩ-500 V position.

3.2 SOFTWARE VERSION

To view the internal software version of the instrument, keep the DISPLAY button
pressed and turn the switch to the MΩ-1000 V position.
NOTE:
Technical documentation on Understanding Insulation
Resistance Testing is available at www.aemc.com/understanding-irt.

3.3 VOLTAGE MEASUREMENT

As soon as the switch is set to an insulation measurement position, the
instrument automatically measures the presence of any AC/DC voltage. This
voltage is measured at all times and indicated on the small display unit.
The instrument automatically determines AC or DC. The AC measurement is an
RMS value.
If an excessively high external voltage is present on the terminals (> 0.4 Un),
pressing the START/STOP button will have no effect, and no measurements
will be made. Similarly, if an excessively high erroneous voltage (> 0.4 Un) is
detected during the measurement, the measurement will automatically stop.
Megohmmeter Model 6505 - User Manual

3. OPERATION

.
13