Deif AGC 200 Series General Manuallines For Commissioning

Deif AGC 200 Series General Manuallines For Commissioning

Automatic genset controller
Hide thumbs Also See for AGC 200 Series:

Advertisement

GENERAL GUIDELINES FOR COMMISSIONING
DEIF A/S · Frisenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · info@deif.com · www.deif.com
MULTI-LINE 2
● Settings check
● Governor check
● AVR check
● Protections check
● Adjustment
● Troubleshooting
Document no.: 4189340703C
SW version:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AGC 200 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Deif AGC 200 Series

  • Page 1 ● Troubleshooting DEIF A/S · Frisenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · info@deif.com · www.deif.com isenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · info@deif.com · www.deif.com Document no.: 4189340703C...
  • Page 2: Table Of Contents

    5.5.4. EIC, J1939 ..........................15 6. AVR check 6.1. Instructions............................17 6.1.1. Instructions..........................17 6.2. Voltage setting............................17 6.2.1. Voltage setting..........................17 6.2.2. Relay output..........................17 6.2.3. Analogue output...........................17 6.3. Voltage droop............................17 6.3.1. Voltage droop..........................17 6.4. Voltage range............................18 DEIF A/S Page 2 of 25...
  • Page 3 8.3.1. Relay output adjustments......................23 8.4. Resulting speed/voltage curve upon load change................23 8.4.1. Resulting speed/voltage curve upon load change...............23 9. Troubleshooting 9.1. Troubleshooting for Multi-line 2 and Uni-line products................. 25 9.1.1. Remedy of problem........................25 DEIF A/S Page 3 of 25...
  • Page 4: Delimitation

    4189340703 UK 1. Delimitation 1.1 Scope of General guidelines for commissioning 1.1.1 Scope of document This document covers the following products: AGC 200 series SW version 3.5x.x or later AGC-3 SW version 3.3x.x or later AGC-4 SW version 4.0x.x or later GPC-3/GPU-3 Hydro SW version 3.0x.x or later...
  • Page 5: General Information

    2.1.2 Legal information and disclaimer DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate the engine/generator controlled by the Multi-line 2 unit, the company responsible for the installation or the operation of the set must be contacted.
  • Page 6: Factory Settings

    2.2 About the guidelines 2.2.1 General purpose This document includes general guidelines for commissioning of DEIF’s Multi-line 2 units. It mainly includes instructions for settings, governor, AVR and protections check and unit adjustment. The general purpose of the document is to supply general guidelines to be used in the commissioning of the Multi-line 2.
  • Page 7: Step By Step

    Multi-line 2 unit. Step 1 Settings check Step 2 Governor check Step 3 AVR check Step 4 Protections check Step 5 Adjustment In addition, the generic troubleshooting in the chapter "Troubleshooting" can be used. DEIF A/S Page 7 of 25...
  • Page 8: Settings

    The nominal values of the Multi-line 2 are adjusted in the general part of the system setup menu. In the PC utility software, it is presented as illustrated on the above screen dump. The correct values are sup- plied by the switchboard manufacturer. DEIF A/S Page 8 of 25...
  • Page 9: Alarm Settings

    In the PC utility software, it is presented as illustrated on the screen dump above or similar. The number of alarms depends on the options selection of the individual unit. The actual alarm parameters are adjusted ac- cording to costumer requirements and application requirements. DEIF A/S Page 9 of 25...
  • Page 10: Function Control Settings

    Multi-line 2, they must be stepped through carefully. The function control settings are adjusted according to the desired unit control. In need of detailed information about the requirements, contact the switchboard manufacturer. DEIF A/S Page 10 of 25...
  • Page 11: Synchronisation Settings

    The screendump below illustrates the controller settings related to the speed governor. As an initial setting before the first start up, the K of the frequency and power controllers are set to a low value giving a slow regulation. DEIF A/S Page 11 of 25...
  • Page 12: Voltage Controller Settings

    , Ti and Td of the frequency and power controllers are set to a value giving a slow regulation. This means that K and Td should be set to a low value, and Ti should be set to a high value. DEIF A/S Page 12 of 25...
  • Page 13: Governor Check

    (150 Ω gives 3V DC at 20 mA, etc). The AGC 200 series has no analogue outputs. If analogue outputs are needed, the IOM 200 series external interface unit must be used.
  • Page 14: Speed Droop

    Multi-line 2 is not in control). In order to ensure equal load sharing on parallel running machines, all gov- ernors must have the same droop setting. DEIF recommends adjusting the speed droop on the speed governor for stability purposes. It is necessary in all cases when relay outputs for governor control is used.
  • Page 15: Analogue Interfacing

    Direct digital signals Multi-line 2 down down 5.5.3 Analogue interfacing Direct analogue signal Multi-line 2 ±25mA External potmeter Multi-line 2 ±25mA 5.5.4 EIC, J1939 The interface is between CAN L and CAN H. DEIF A/S Page 15 of 25...
  • Page 16 Governor check 4189340703 UK Deif unit Engine system CANbus interface CANbus interface 120 Ω 120 Ω For additional information about interfaces, see the document "Interfacing DEIF Equipment, application notes 4189340670 UK" available on www.deif.com. DEIF A/S Page 16 of 25...
  • Page 17: Avr Check

    (150 Ω gives 3V DC at 20 mA etc). The AGC 200 series has no analogue outputs. If analogue outputs are needed, the IOM 200 series external interface unit must be used.
  • Page 18: Voltage Range

    +/-25 mA or 0-20 mA signal from the Multi-line 2 is applied. This signal can be converted to the nec- essary voltage level. When the digital interfacing is used, two relays are used as increase/decrease outputs. The AGC 200 series has no analogue outputs. If analogue outputs are needed, the IOM 200 series external interface unit must be used.
  • Page 19: Protections

    (trip of non-essential load, breaker tripping and engine stopping). The switchboard manufacturer and the end customer must take these considerations. 7.1.3 Configuration of the protections The dialogue box shows a typical alarm. DEIF A/S Page 19 of 25...
  • Page 20 In this example, the generator reverse power setpoint is -5%. If the commissioning is done without the PC utility software, the timers can be seen in the serv- ice menu 9120. DEIF A/S Page 20 of 25...
  • Page 21: Adjustment

    Adjust the Ti to approx. 1.5-1.7 times the value where insta- bility begins. 8.2.4 Step 3, adjustment of the Td Step by step increase the Td until the genset becomes unstable. Adjust the Td to 50…70% of the value. DEIF A/S Page 21 of 25...
  • Page 22: Step 4, Readjustment Of Controller Settings

    AVR is underlined. When changing the setp value, an off- set will be added to or subtracted from the nominal value. The reg. value is the output value from the regula- DEIF A/S Page 22 of 25...
  • Page 23: Auto And Test Mode (Agc 200/Agc-3/Agc-4 Only)

    8.4 Resulting speed/voltage curve upon load change 8.4.1 Resulting speed/voltage curve upon load change Testing is easily done by using (if possible) a load bank applying "jumps" in the generator load, hereby testing the speed/voltage control. DEIF A/S Page 23 of 25...
  • Page 24 The optimum result is indicated by this curve: Freq/voltage Load change (increase) Frequency/voltage Nominal frequency/voltage Time As indicated, 2-3 "overshoots" before stabilising after a sudden change is OK. If more "overshoots" are present, decrease the K factor and try again. DEIF A/S Page 24 of 25...
  • Page 25: Troubleshooting

    Speed decreases when increase was ex- Outputs "+" and "-" re- Swap connections. pected (analogue output). versed. Engine overspeeds when starting up. Regulator output is too Decrease the analogue output high. signal by decreasing the resis- tor. DEIF A/S Page 25 of 25...

This manual is also suitable for:

Agc-3Gpc-3Gpu-3 hydroAgc pmGpu-3Agc-4 ... Show all

Table of Contents