DC Power Electrical Safety Warnings for Juniper Networks Devices

DC Power Copper Conductors Warning

226
Be sure to connect the ground wire or conduit to a solid office (earth) ground. A closed
loop ring is recommended for terminating the ground conductor at the ground stud.
Ensure that the polarity of the DC input wiring is correct. Under certain conditions,
connections with reversed polarity might trip the primary circuit breaker or damage
the equipment.
For personal safety, connect the green and yellow wire to safety (earth) ground at both
the router and the supply side of the DC wiring.
The marked input voltage of –48 VDC for a DC-powered router is the nominal voltage
associated with the battery circuit, and any higher voltages are only to be associated
with float voltages for the charging function.
Because the router is a positive ground system, you must connect the positive lead to
the terminal labeled
, the negative lead to the terminal labeled
+
to the chassis grounding points.
DC Power Electrical Safety Warnings for Juniper Networks Devices on page 226
When working with DC-powered equipment, observe the following warnings:
DC Power Copper Conductors Warning on page 226
DC Power Disconnection Warning on page 227
DC Power Wiring Terminations Warning on page 228
WARNING:
Use copper conductors only.
Waarschuwing Gebruik alleen koperen geleiders.
Varoitus Käytä vain kuparijohtimia.
Attention Utilisez uniquement des conducteurs en cuivre.
Warnung Verwenden Sie ausschließlich Kupferleiter.
Avvertenza Usate unicamente dei conduttori di rame.
Advarsel Bruk bare kobberledninger.
Aviso Utilize apenas fios condutores de cobre.
¡Atención! Emplee sólo conductores de cobre.
Varning! Använd endast ledare av koppar.
, and the earth ground