Parallel Redundancy Protocol (Prp); Txgoose Status - GE B90 Instruction Manual

Low impedance bus differential system
Hide thumbs Also See for B90:
Table of Contents

Advertisement

STATUS
These values specify the remaining number of TCP connections still available for each protocol. The display depends on the
options applicable to your device. Each time a connection is used, the remaining number of connections decrements.
When released, the remaining number of connections increments. If no connection is made over the specific protocol, the
number equals the maximum number available for the specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus TCP
status shows 4.
— The number of IEC 61850 connections remaining.
MMS TCP

6.3.15 Parallel Redundancy Protocol (PRP)

The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation
networks.
ACTUAL VALUES  STATUS  PRP STATUS
 PRP STATUS
6
The B90 is provided with optional PRP capability. This feature is specified as a software option at the time of
ordering. See the Order Codes section in chapter 2 for details.
Total Received Port A
Total Received Port B
is a counter for total messages received with an error (bad port code, frame length too short).
Total Errors
Mismatches Port A
and LAN ID in the frame do not match).
Mismatches Port B
and LAN ID in the frame do not match).

6.3.16 TxGOOSE status

ACTUAL VALUES  STATUS  TxGOOSE STATUS
 TxGOOSE STATUS
6-8
DNP TCP(max 2)
2
IEC-104 TCP(max 2)
2
SFTP (max 4)
4
Total Rx Port A:
Total Rx Port B:
Mismatches Port A:
Mismatches Port B:
Total Errors:
is a counter for total messages received (either from DANPs or from SANs) on Port A.
is a counter for total messages received (either from DANPs or from SANs) on Port B.
is a counter for total messages received with an error on Port A (PRP frame, but port received through
is a counter for total messages received with an error on Port B (PRP frame, but port received through
R-TxGOOSE 1
ARP:
Range: 0 to 2
Range: 0 to 2
Range: 0 to 4
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: 0 to 4G, blank if PRP disabled
Range: On, Off
Off