Directional Principle; Current Directional Protection - GE UR Series B30 Instruction Manual

Bus differential system
Hide thumbs Also See for UR Series B30:
Table of Contents

Advertisement

9 THEORY OF OPERATION

9.4DIRECTIONAL PRINCIPLE

For better security, the B30 uses the current directional protection principle to dynamically supervise the main current differ-
ential function. The directional principle is in effect permanently for low differential currents (Region 1 in Figure 9–4: Two
Regions of Differential Characteristic) and is switched on dynamically for large differential currents (Region 2 in the same
figure) by the saturation detector (see Section 9.5: Saturation Detector) upon detecting CT saturation.
The directional principle responds to a relative direction of the fault currents. This means that a reference signal, such as
bus voltage, is not required. The directional principle declares that
if all of the fault currents flow in one direction, the fault is internal, or
if at least one fault current flows in an opposite direction compared with the sum of the remaining currents, the fault is
external.
The directional principle is implemented in two stages.
First, based on the magnitude of a given current, it is determined whether the current is a fault current. If so, its relative
phase relation has to be considered. The angle check must not be initiated for the load currents as the direction will be out
of the bus even during internal faults. The auxiliary comparator of this stage applies an adaptable threshold. The threshold
is a fraction of the restraining current. The current from a particular feeder is used for bus directional comparison if its mag-
nitude is greater than K × I
restraint
zones with three to six feeders, K = 0.8 / (N – 1). For bus zones with more than six feeders, K = 0.16.
Second, for – and only for – the selected fault currents, the phase angle between a given current and the sum of all the
remaining currents is checked. The sum of all the remaining currents is the differential current less the current under con-
sideration. Therefore, for each, say the pth, current to be considered, the angle between the
checked.
Ideally, during external faults, the said angle is close to 180° (see below); and during internal faults - close to 0 degrees.
Figure 9–5: DIRECTIONAL PRINCIPLE OPERATION DURING EXTERNAL FAULTS
Figure 9–6: DIRECTIONAL PRINCIPLE OPERATION DURING INTERNAL FAULTS
The B30 implementation calculates the maximum angle for the considered currents and compares it against a fixed thresh-
old of 90°. The flag indicating whether the directional protection principle is satisfied is available as the FlexLogic™ oper-
and
.
BUS 1(2) DIR
GE Multilin
or it is greater than 2 times its CT rating. For bus zones with two feeders, K = 0.2. For bus
External Fault Conditions
I
p
imag
I
I
OPERATE
D
p
BLOCK
I
- I
D
p
BLOCK
OPERATE
Internal Fault Conditions
I
p
imag
I
I
OPERATE
D
p
BLOCK
BLOCK
OPERATE
B30 Bus Differential System
9.4 DIRECTIONAL PRINCIPLE

9.4.1 CURRENT DIRECTIONAL PROTECTION

I
P
I
p
real
I
I
I
D
p
p
836726A2.CDR
I
p
I
- I
real
D
p
I
I
D
p
I
p
836727A2.CDR
and
I
I
phasors is to be
D
P
9-7
9

Advertisement

Table of Contents
loading

Table of Contents