Lenovo x3650 M4 BD 5466 Installation And Service Manual page 382

Hide thumbs Also See for x3650 M4 BD 5466:
Table of Contents

Advertisement

1.
Use the IBM Power Configurator utility to determine current system power
consumption. For more information and to download the utility, go to
http://www-03.ibm.com/systems/bladecenter/resources/powerconfig.html.
2. Follow actions in "Power Problems and Solving Power Problems".
If the specified sensor is PS n 12V OV Fault, complete the following steps until the problem is solved:
1. Check power supply n LED.
2. Remove the failing power supply.
3. (Trained technician only) Replace the system board. (n = power supply number)
If the specified sensor is PS n 12V UV Fault, complete the following steps until the problem is solved:
1. Check power supply n LED.
2. Remove the failing power supply.
3. Follow actions in "Power Problems and Solving Power Problems".
4. (Trained technician only) Replace the system board. (n = power supply number)
If the specified sensor is PS n 12Vaux Fault, complete the following steps until the problem is solved:
1. Check power supply n LED.
2. Replace power supply n. (n = power supply number)
• 80070614-2201ffff : Sensor [SensorElementName] has transitioned to non-recoverable. (TPM Phy
Pres Set)
This message is for the use case when an implementation has detected a Sensor transitioned to
non-recoverable.
May also be shown as 800706142201ffff or 0x800706142201ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Other
SNMP Trap ID
50
CIM Information
Prefix: PLAT ID: 0530
User Response
1. Update the server firmware (see Recovering the server firmware).
2. If the problem persists, (trained technician only) replace the system board (see Removing the
system board and Installing the system board).
368
Lenovo System x3650 M4 BDInstallation and Service Guide