Lenovo x3650 M4 BD 5466 Installation And Service Manual page 354

Hide thumbs Also See for x3650 M4 BD 5466:
Table of Contents

Advertisement

SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0494
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffle is in place and correctly installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Make sure that the heat sink for microprocessor n.
4. (Trained technician only) Replace system board.
• 80010901-0c01ffff : Numeric sensor [NumericSensorElementName] going high (upper critical) has
asserted. (Ambient Temp)
This message is for the use case when an implementation has detected an Upper Critical sensor going
high has asserted.
May also be shown as 800109010c01ffff or 0x800109010c01ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0494
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffle is in place and correctly installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Make sure that the heat sink for microprocessor n.
4. (Trained technician only) Replace system board.
340
Lenovo System x3650 M4 BDInstallation and Service Guide