Lenovo x3650 M4 BD 5466 Installation And Service Manual page 366

Hide thumbs Also See for x3650 M4 BD 5466:
Table of Contents

Advertisement

CIM Information
Prefix: PLAT ID: 0498
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffle is in place and correctly installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Make sure that the heat sink for microprocessor n.
4. (Trained technician only) Replace system board.
80010b01-1405ffff : Numeric sensor [NumericSensorElementName] going high (upper
non-recoverable) has asserted. (DIMM EF VR Temp)
This message is for the use case when an implementation has detected an Upper Non-recoverable
sensor going high has asserted.
May also be shown as 80010b011405ffff or 0x80010b011405ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0498
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffle is in place and correctly installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Make sure that the heat sink for microprocessor n.
4. (Trained technician only) Replace system board.
80010b01-1406ffff : Numeric sensor [NumericSensorElementName] going high (upper
non-recoverable) has asserted. (DIMM GH VR Temp)
352
Lenovo System x3650 M4 BDInstallation and Service Guide

Advertisement

Table of Contents
loading

Table of Contents