Bsf; Bsm; Bso; Bsp - AMX MVP-9000i-GB Instruction Manual

Table of Contents

Advertisement

"^" Button Commands (Cont.)

^BSF

^BSM

^BSO

^BSP

^BVL

^BVN

MVP-9000i - Instruction Manual
Set the focus to the text area.
Note: Select one button at a time (single variable text address). Do not assign a variable text address range to set focus to
multiple buttons. Only one variable text address can be in focus at a time.
Syntax:
"'^BSF-<vt addr range>,<selection value>'"
Variable:
variable text address range = 1 - 4000.
selection value = Unselect = 0 and select = 1.
Example:
SEND_COMMAND Panel,"'^BSF-500,1'"
Sets the focus to the text area of the button.
Submit text for text area buttons. This command causes the text areas to send their text as strings to the NetLinx Master.
Syntax:
"'^BSM-<vt addr range>'"
Variable:
variable text address range = 1 - 4000.
Example:
SEND_COMMAND Panel,"'^BSM-500'"
Submits the text of the text area button.
Set the sound played when a button is pressed. If the sound name is blank the sound is then cleared. If the sound name is
not matched, the button sound is not changed.
Syntax:
"'^BSO-<vt addr range>,<button states range>,<sound name>'"
Variable:
variable text address range = 1 - 4000.
button states range = 1 - 256 for multi-state buttons (0 = All states, for General buttons 1 = Off state and
2 = On state).
sound name = (blank - sound cleared, not matched - button sound not changed).
Example:
SEND_COMMAND Panel,"'^BSO-500,1&2,music.wav'"
Assigns the sound 'music.wav' to the button Off/On states.
Set the button size and its position on the page.
Syntax:
"'^BSP-<vt addr range>,<left>,<top>,<right>,<bottom>'"
Variable:
variable text address range = 1 - 4000.
left = left side of page.
top = top of page.
right = right side of page.
bottom = bottom of page.
Example:
SEND_COMMAND Panel,"'^BSP-530,left,top'"
Sets the button with variable text 530 in the left side top of page.
Log-On/Log-Off the computer control connection.
Syntax:
"'^BVL-<vt addr range>,<connection>'"
Variable:
variable text address range = 1 - 4000.
connection = 0 (Log-Off connection) and 1 (Log-On connection).
Example:
SEND_COMMAND Panel,"'^BVL-500,0'"
Logs-off the computer control connection of the button.
Set the computer control remote host for the specified address.
Syntax:
SEND_COMMAND <DEV>,"'^BVN-<vt addr range>,<remote host>'"
Variables:
variable text address range = 1 - 4000.
remote host = 1 - 50 ASCII characters.
Example:
SEND_COMMAND Panel,"'^BVN-500,191.191.191.191'"
Sets the remote host to '191.191.191.191' for the specific computer control button.
Programming
109