20.3.41 Staircase lighting details
20.3.41.1 Behaviour
If this module receives the value 1 (logical "true") via the Input 0, it immediately outputs it on
the Output 0. After expiry of a delay time, the value 0 (logical "false") is output on the Output 0.
The delay time (in seconds) is dependent on the value at Input 1.
Via a value at Input 2 , a number of pulses can be defined that are output before expiry of the
delay time on the Output 0. A pulse consists of a 0-1 combination with an interval of 0.5 se-
conds between the values 0 an 1.
If invalid values are specified for the delay time or number of pulses (e.g. -1), the result 1 (logi-
cal "true") is output on the Output 1.
The data type of the Input 0 is Boolean, the data types of the Inputs 1 and 2 are Number. If ne-
cessary, incoming values are converted before the calculation (see conversion table below).
20.3.41.2 Extended settings
Via the Restart timer parameter, you can specify whether the delay time shall always be reset by
the receipt of the value 1 via the Input 0.
20.3.41.3 Conversion table
Boolean
(converted)
Boolean ---
0
Number
≠ 0
DPTTime true
DPTDate true
String
"0" or ""
223/240
Number
(converted)
true
false
true
→
---
→
false
Milliseconds
since 1.1.1970
Number
→
false Number, if possible;
→
1
→
0
→