Extended Settings; Conversion Table; Area Tester (External) Module Details; Behaviour - Busch-Jaeger Busch-ComfortTouch Product Manual

Table of Contents

Advertisement

20.3.18 Area tester (external) module details

20.3.18.1 Behaviour

The module checks whether the incoming comparison value on Input 0 lies outside two limit
values. The limit values are defined by the Input 1 and the Input 2. If the comparison value is
outside the limit values, the result 1 (logical "true") is output on Output 0. Otherwise the output
value is 0 (logical "false"). Output 1 always outputs the result inverted. If the limit values are
invalidly configured (e.g. upper limit less than lower limit) the result 1 (logical "true") is output
on Output 2.
If necessary, incoming values are converted into the internal data type of the module before the
comparison (see conversion table below). Thus, observe the selection of a correct internal data
type!
The comparison is dependent on the internal data type of the module and is executed in the fol-
lowing way:
Internal data
Comparison rule
type
Number
Nummer comparison
Time
Time comparison
Date
Date comparison
String length compari-
String
son

20.3.18.2 Extended settings

Internal data type
Via the
the module.
Only send with change
Via the
value shall only be sent if the result of the calculation is different to the previ-
ously calculated result.

20.3.18.3 Conversion table

Example
3 ≤ 9 ≤ 7
15:30 ≤ 21:10 ≤ 19:00
1.1.1970 ≤ 29.12.2009 ≤
17.5.2009
"priOn" ≤ "" ≤ "ComfortPanel"
parameter, you can specify the internal data type of
parameter, you can specify whether an output
→ false
→ false
→ false
→ false
178/240