The library is calibrated before shipment. Under normal operating
conditions, you do not need to calibrate the library. However, you
may be asked by Exabyte's technical support personnel to
calibrate the library as part of a troubleshooting procedure.
When you calibrate the library, the robot's laser first scans the
calibration targets on the data cartridge magazines and the
calibration block (in the calibration block slot). The robot then
picks the calibration block from the calibration block slot and
places it into the fixed cartridge slot and the tape drives. The
robot's laser scans the calibration targets in each location to
determine their exact position.
Installation and Operation
If necessary, disable security (see
Change the control mode to LCD (see
Open the library door and make sure the calibration block is
located in the calibration block slot. (See
of the calibration block slot.)
Remove any cartridge from the fixed cartridge slot. Then, close
and lock the door.
empty before you calibrate the library.
Make sure all six data cartridge magazines are
installed before you calibrate the library.
page
page
Make sure the fixed cartridge slot is
Library Status
73).
95).
page 5
for the location