CHAPTER 3 BASIC OPERATION

3.2 Setting Input Specifications

+ Input type
3–4
Setting input specifications
Input type
Temperature input?
Y
Temperature unit
Temperature input shift
End of setup
With temperature input, scaling and decimal point parameters need not
be set as this information is determined by the input (sensor) type.
(These parameters are not displayed.) Note that temperature unit and
temperature input shift parameters need to be set.
With analog input, the scaling upper limit", scaling lower limit" and
decimal point" parameters need to be set.
Set the type No. (0 to 22) in the input type" parameter (Set up mode).
The factory setting is 2: K (thermocouple)."
For details on input types and setting ranges, see page 5 25.
Setup mode
N
Scaling
Decimal point
Level 2 mode