CHAPTER 4 APPLIED OPERATION
+ Remote SP
monitor
+ SP tracking
+ Operating
conditions
Parameters
4–8
In the remote SP mode, the remote SP can be monitored on the No.2 dis
play for PV/SP . In the local SP mode, the remote SP can be monitored in
the remote SP monitor" parameter.
When the local SP is switched to from the remote SP when the SP track
ing function is enabled, the local SP is changed so that the remote SP
value is held at the SP value used immediately before switching.
To use the SP tracking function, set the SP tracking" parameter to
ON".
The following figure shows how SP tracking works when the SP mode
is switched.
LSP1
LSP2
RSP2
SP mode
LSP
(1) When the remote SP is switched to when the set point is LSP1", the
SP is switched to RSP2".
(2) The SP shifts according to remote SP input.
(3) When the local SP is switched to, the set point becomes LSP2" if the
SP tracking function is enabled. If this function is disabled, the SP
will be switched to LSP1".
When the local SP is switched to the remote SP , the SP ramp will operate
if the SP ramp function is enabled.
During auto tuning, remote SP input is not accepted. Auto tuning is
executed on the set point at the start of auto tuning.
Remote SP is not subject to the standby sequence reset conditions.
Symbol
Parameter Name: Mode
Remote SP enable
Remote SP upper limit : Option
Remote SP lower limit : Option
SP mode
SP tracking
RSP input
RSP
LSP
: Option
Remote SP function
RSP scaling
RSP scaling
: Level 2
LSP/RSP switching
SP tracking
: Option