CHAPTER 5 PARAMETERS
Expansion Mode
Standby sequence reset method
Selects the conditions for enabling reset after the standby sequence of the alarm has
been canceled.
Condition A:
Function
Control started (including power ON), and, alarm value, input shift value or set point
(except for changing SP mode or during Remote SP) changed.
Condition B:
Power ON
The following illustration shows an operation example for the lower limit alarm with
standby sequence.
(after change)
Alarm Output: Condition A
Alarm Output: Condition B
Comment
F Related parameters
Alarm 1 type" Alarm 2 type" Alarm 3 type" (setup mode)
See
Automatic return of display mode
If you do not operate any of the controller keys for the time set in this parameter when
in levels 0 to 2 modes, the display automatically returns to the PV/SP display.
When this parameter is set to 0", this function is disabled. (The screen will not
Function
change automatically.)
This parameter is invalid while the menu is displayed.
Comment
5–34
SP value change
Alarm point
Alarm point
Setting Range
0: Condition A / 1: Condition B
Unit
Setting Range
0 to 99
Second
Condition A only
Alarm hysteresis
f : Standby sequence release point
Condition A only
F : Standby sequence restart point
Default
0
Default
0