Advertisement

Dead band
Sets the output dead band width in a heating and cooling control system. A negative
setting sets an overlap band.
Function
Setting Range
-19.99 to 99.99
Comment
F Related article
4.1 Selecting the Control Method (page 4 2)
See
Manual reset value
Sets the required manipulated variable to remove offset during stabilization of P or
PD control.
Function
Setting Range
0.0 to 100.0
Comment
Conditions of Use
The control system must be heating and
cooling control.
Unit
Default
%FS
0.00
Conditions of Use
The control must be either standard con-
trol or 2-PID control, and the "integral
time" parameter must be set to "0".
Unit
Default
%
50.0
Level 1 Mode
5–13