Omron E5EK - MANUAL 2 User Manual page 78

Digital controller compobus/d (devicenet) type
Hide thumbs Also See for E5EK - MANUAL 2:
Table of Contents

Advertisement

MV upper limit
MV lower limit
MV change rate limit
The MV upper limit" and MV lower limit" parameters set the upper and lower lim
its of the manipulated variable. When the manipulated variable calculated by the
E5EK DRT controller is outside of the upper and lower limit range, the upper limit
Function
or lower limit set to these parameters is output, respectively.
The MV change rate limit" parameter sets the maximum permissible change width
per second of the manipulated variable. If a change in the manipulated variable
causes this parameter setting to be exceeded, the calculated value is reached while
changing the value by the per second value set in this parameter.
This function is disabled when the set value is 0.0".
MV upper limit
The setting ranges during standard control and heating and cooling control are dif
ferent. Also, the manipulated variable at the cooling side during heating and cooling
Comment
control is expressed as a negative value.
Control Method
Standard
Heating and cooling
MV lower limit
The setting ranges during standard control and heating and cooling control are dif
ferent. Also, the manipulated variable at the cooling side during heating and cooling
control is expressed as a negative value.
Control Method
Standard
Heating and cooling
MV change rate limit
Setting Range
0.0 to 100.0
F Related article
4.2 Operating Condition Restrictions/Manipulated variable restrictions (page 4 4)
See
Conditions of Use
The control must be 2-PID control
Setting Range
MV lower limit +0.1 to 105.0
0.0 to 105.0
Setting Range
-5.0 to MV upper limit -0.1
-105.0 to 0.0
Unit
Default
%/S
0.0
Level 2 Mode
Unit
Default
%
105.0
%
105.0
Unit
Default
%
-5.0
%
-105.0
5–21