_C/_F selection
This parameter can be used when thermocouple or platinum resistance thermometer
is selected as the input type.
Set the temperature input unit to either of _C" or _F".
Function
Comment
F Related article
3.2 Setting Input Specifications (page 3 4)
F Related parameter
See
Input type" (setup mode)
Control output 1
assignment
Control output 2
assignment
Assigns the output functions to either of control output 1 or 2.
The following seven output functions can be assigned as outputs:
Control output (heat), Control output (cool), Alarms 1 to 3, HBA, and LBA.
Function
Errors 1, 2 and 3 cannot be assigned as outputs.
When the output function assigned to control output 1 or control output 2 is ON, the
OUT1" or OUT2" LED lights. However, note that the LED does not light when con
trol output (heat) or control output (cool) are assigned to linear outputs such as current
and voltage.
When the output function assigned to control output 2 is ON, the OUT2" LED lights.
Symbol
Function
Comment
Defaults:
Control output 1" = [
F Related article
3.3 Setting Output Specifications (page 3 7)
F Related parameters
See
Alarm related parameters
Heating and cooling related parameter
LBA detection time" (level 2 mode)
Default
Setting Range
: _C /
: _F
Control output
(heat)
Conditions of Use
The input type must be set to temperature
input (thermocouple or platinum resis-
tance thermometer).
Conditions of Use
The control must be standard control or
heating and cooling control.
Control output
Alarm 1 Alarm 2 Alarm 3
(cool)
], Control output 2" = [
Setup Mode
HBA
LBA
]
5–27