Omron E5EK - MANUAL 2 User Manual page 97

Digital controller compobus/d (devicenet) type
Hide thumbs Also See for E5EK - MANUAL 2:
Table of Contents

Advertisement

CHAPTER 5 PARAMETERS
Option Mode
Remote SP upper limit
Remote SP lower limit
Sets the remote SP upper and lower limit values. The upper limit value is equivalent
to 20 mA, and the lower limit value is equivalent to 4 mA. Set the upper limit value
in the remote SP upper limit" parameter and the lower limit value in the remote
Function
SP lower limit" parameter.
When the SP setting upper limit" and SP setting lower limit" parameters are
changed, the remote SP upper and lower limit values are forcibly changed to the SP
setting upper and lower limit values.
Comment
F Related article
4.3 How to Use the Remote SP (page 4 7)
F Related parameters
See
Decimal point" (setup mode)
SP setting upper limit" SP setting lower limit" (expansion mode)
Remote SP enable" (option mode)
5–40
RSP
Upper limit value
Lower limit value
Parameter
Remote SP upper limit
SP setting lower limit to SP setting upper limit
Remote SP lower limit
SP setting lower limit to SP setting upper limit
Conditions of Use
The remote SP function must be enabled.
4
20
Setting Range
Input (mA)
Unit
Default
EU
1300
EU
-200

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5ekdrt

Table of Contents