Control period (heat)
Control period (cool)
Sets the pulse output period. Set the control period taking the control characteristics
and life expectancy of the controller into consideration.
In standard control, use the control period (heat)" parameter. The control period
Function
(cool)" parameter cannot be used.
In heating and cooling control, the control period can be set independently for heat
ing and cooling. Use the control period (heat)" parameter to set the heating side con
trol period, and use the contrlo period (cool)" parameter to set the cooling side con
trol period.
Control period (heat)
Control period (cool)
Comment
F Related article
3.3 Setting Output Specifications (page 3 7)
F Related parameters
See
Control output 1 assignment" Control output 2 assignment" (setup mode)
Heater current monitor
Measures the current value of the heater from CT input.
This parameter is not displayed when the linear output unit (E53 Cj, E53 Vj) is
mounted.
Function
Monitor Range
0.0 to 55.0
[
Monitor
F Related article
4.4 How to Use the Heater Burnout Alarm (page 4 9)
F Related parameters
See
Heater burnout" (level 1 mode) HBA latch" (option mode)
Parameter
Setting Range
1 to 99
1 to 99
Unit
A
] is displayed when 55.0 A is exceeded.
Level 1 Mode
Conditions of Use
Relay, SSR or voltage output must be set
as the outputs, and the control must be set
to 2-PID control, standard control or heat-
ing and cooling control.
Unit
Default
Second
20
Second
20
Conditions of Use
The HBA output function must be
assigned.
5–15