Omron E5EK - MANUAL 2 User Manual page 123

Digital controller compobus/d (devicenet) type
Hide thumbs Also See for E5EK - MANUAL 2:
Table of Contents

Advertisement

7.4 Calibrating Current Input
' Preparation
' Calibration
10
SOURCE
9
8
7
6
5
4
3
2
1
In the above figure, STV refers to a standard DC current/voltage source.
(1) When [
] is displayed, the 30 minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.
(2) Press the
key. The display changes to [
display). Set the STV output to 20mA. When the value on the No.2 dis
play has stabilized (changes of several digits max.), press the
to temporarily store the calibration data.
(3) Press the
key. The display changes to [
play). Set the STV output to 0 mA. When the value on the No.2 display
has stabilized (changes of several digits max.), press the
temporarily store the calibration data.
(4) Press the
key until the display changes to the data save display.
Press the
key. The No.2 display changes to [
seconds later the calibration data is saved to internal memory. If you
press the
key when the No.2 display reads [
data is invalidated.
(5) This completes calibration of current input. Press the
return the display to [
7.4 Calibrating Current Input
20
21 22
19
18
17
16
15
14
13
12
23
11
+
STV
].
] (20mA calibration
key
] (0mA calibration dis
key to
], and two
], the calibration
key to
7–9