' Calibration :
0 to 10VDC
(1) When [
] is displayed, the 30 minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.
(2) Press the
key. The display changes to [
display). Set the STV output to 10VDC. When the value on the No.2
display has stabilized (changes of several digits max.), press the
key to temporarily store the calibration data.
(3) Press the
key. The display changes to [
play). Set the STV output to 0V . When the value on the No.2 display
has stabilized (changes of several digits max.), press the
temporarily store the calibration data.
(4) Press the
key until the display changes to the data save display.
Press the
key. The No.2 display changes to [
seconds later the calibration data is saved to internal memory. If you
press the
key when the No.2 display reads [
data is invalidated.
(5) This completes calibration of voltage input (0 to 10VDC). Press the
key to return the display to [
7.5 Calibrating Voltage Input
] (10VDC calibration
] (0V calibration dis
], and two
], the calibration
].
key to
7–11