CHAPTER 5 PARAMETERS
Level 1 Mode
Proportional band
Integral time
Derivative time
Sets the PID parameters. However, note that the PID parameter settings are changed
to optimum values when auto tuning is executed.
Function
Comment
F Related parameter
AT Execute/Cancel" (level 1 mode)
See
Cooling coefficient
In heating and cooling control, P at the cooling side is calculated by the following for
mula:
Cooling side P = cooling coefficient P
Function
Comment
F Related article
4.1 Selecting the Control Method (page 4 2)
F Related parameter
See
Proportional band" (level 1 mode)
5–12
Parameter
Setting Range
Proportional band
Integral time
Derivative time
Unit
Setting Range
0.01 to 99.99
None
Conditions of Use
Control must be 2-PID control.
Unit
0.1 to 999.9
%FS
0 to 3999
Second
0 to 3999
Second
Conditions of Use
The control must be either heating and
cooling control, or 2-PID control.
Default
1.00
Default
10.0