Data - Omron trajexia CJ1W-MCH72 Operation Manual

Sysmac cj-series programmable controller
Hide thumbs Also See for trajexia CJ1W-MCH72:
Table of Contents

Advertisement

Data

3-3
Data
3-3-1
Control and status data
3-3-1-1 Control data
Note
62
Two types of data are exchanged during a data exchange:
Control and status data
Configurable data
The CJ1W-MCH72 has 13 control and status words.
The control and status data is in the PLC CIO memory at word location n,
where n is equal to 1500 + 25 × unit_number.
The PLC program can directly control the CJ1W-MCH72 with control word n. It
can execute the following functions:
/i
Word
Bit
Description
n
0
Enable execution
1
Enable watchdog
2
Deceleration stop
3
Enable outputs
4-15
Reserved
Setting bit 2 to 0 has no function.
Value
0
No BASIC programs can be executed
0
Allow BASIC programs to be executed
1 to 0
Stop BASIC programs, switches off the
axes watchdog, stop all movement,
clear movement buffers and clear the
digital outputs.
0 to 1
Executes
the
configured to run at power-up
0
Forces the watchdog to be off
1
Enables BASIC programs to control the
axes watchdog
1 to 0
Switches off the axes watchdog, stop all
movement and clear movement buffers
0 to 1
Clear movement buffers
0 to 1
Stop
BASIC
deceleration (RAPIDSTOP)
0
Forces digital outputs to be OFF
1
Digital outputs reflect the state of
OP(8..15)
0
-
Section 3-3
Function
programs
that
are
programs
and
start