All BASIC commands
4-2-142 INVERTER_COMMAND
/i
Type
System command
Syntax
INVERTER_COMMAND(0, station, 1, alarm_number)
INVERTER_COMMAND(0, station, 8, mode)
INVERTER_COMMAND(0, station, 7, operation_signals)
Description
INVERTER_COMMAND controls inputs and clears alarm of the Inverter
connected to the system via the MECHATROLINK-II bus.
There are three INVERTER_COMMAND functions:
1: Clears an alarm.
7: Controls operation signals.
8: Set an Inverter to Servo Driver mode, so it acts as a servo axis.
This is possible only for Inverters with an encoder feedback option
card connected.
To use an Inverter via MECHATROLINK-II you must put the command
and the reference via communication option:
Inverter MV/V7: N3=3; N4=9
Inverter F7/G7/V1000: B1-01=3; B1-02=3.
Make sure that the Inverter firmware supports the MECHATROLINK-II
board.
The command returns -1 if successfully executed and 0 if failed.
The command sent to the Inverter corresponds with the bits given in the
table below.
/i
Bit
Value
Command
0
Hex
1
1
Hex
2
2
Hex
4
3
Hex
8
4
Hex
10
5
Hex
20
6
Hex
40
7
Hex
80
8
Hex
100
9
Hex
200
10
Hex
400
11
Hex
800
12
Hex
1000
13
Hex
2000
14
Hex
4000
15
Hex
8000
Description
Run forward
Run reverse
Inverter multifunction Input 3
Inverter multifunction Input 4
Inverter multifunction Input 5
Inverter multifunction Input 6
Inverter multifunction Input 7
Inverter multifunction Input 8 (Only G7)
External fault
Fault reset
Inverter multifunction Input 9 (only G7)
Inverter multifunction Input 10 (only G7)
Inverter multifunction Input 11 (only G7)
Inverter multifunction Input 12 (only G7)
Fault history data clear
External BB command