OUT (T)... Timer output
Bit device
X Y M L F B SB T SM V T C D R W SW Z SD K H
Device
Setting
value
Function
(1) When the operation results before the OUT command are ON, the timer coil will turn ON and
count to the set value. When the time is counted up (count value >= set value), the contacts will
change as shown below.
A contact
B contact Non-continuity
(2) If the operation results before the OUT command turn from ON to OFF, the following will occur.
Timer type
100ms timer
10ms timer
100ms cumulative
timer
(3) The state of the cumulative timer contact after time up will not change until the RST command is
executed.
7. Basic Commands
OUT (T)
Usable device
Word device
Continuity
Timer current
Timer coil
value
OFF
0
Hold current
OFF
value
- 122 -
Get other manuals https://www.bkmanuals.com
Con-
Pointer
stant
P
Setting value
(1 to 32767 is valid)
T0 K50
Device No.(T0 to 255)
Setting value
(1 to 32767 is valid for
the data register details)
T0 D10
Device No.(T0 to 255)
Before time up
A contact B contact A contact B contact
Non-
Continuity Continuity
continuity
Non-
Continuity Continuity Non-
continuity
Digit
No. of
desig-
Index
steps
nation
3
After time up
Non-
continuity
continuity